HP ProLiant BL620c G7 Server series - Removing and Replacing the BBWC Battery Module
 Introduction
This document is provided to assist in removing and replacing the BBWC battery module for the HP ProLiant BL620c G7 Server series.
Minimum skill level
The End User requires no hardware-specific training to replace the defective part. The End user should have familiarity with system hardware and software requiring repair.
Tools required
T15 Screwdriver
T10 Screwdriver
T6 Screwdriver
Parts required
|
NOTE:
|
Part numbers are subject to change. |
| Description
|
Part Number
|
Requires Return
|
| Battery module - For Battery Backed Write Cache (BBWC) |
462976-001 (Modified) |
Yes |
|
NOTE:
|
For customers in countries/regions with RoHS legislation* (e.g. EU,
China, etc.) restricting the use of hazardous substances in electrical
equipment.
The use of the Original Spare part is regulated by RoHS legislation. If your
unit contains a part that is labeled with the Modified Spare number, the
Modified Spare must be ordered as the replacement part.
If your unit contains a part that is labeled with the Original Spare number,
please order the Original Spare as the replacement part. In this case either
the Original Spare or the Modified Spare may be shipped which will not
affect performance or functionality of the unit. |
Summary of instructions
To view a video demonstrating the procedure for removing the BBWC battery module, click on the link below. Or use the product video listing on the HP Services Media Library, (
Click here to go to HP Service Media Library
) then select BBWC battery module
from the menu on the upper left hand side of the screen.
BBWC battery module removal
Review the safety considerations before performing the steps listed below by clicking on the following link:
| CAUTION:
|
Failure to comply with the precautions
could result in damage to your product or loss of data. |
| CAUTION:
|
- To prevent a server blade malfunction or damage to the equipment, do not add or remove the battery pack while an array capacity expansion, RAID level migration, or stripe size migration is in progress.
- After the server blade is powered down, wait 15 seconds and then check the amber LED before unplugging the cable from the cache module. If the amber LED blinks after 15 seconds, do not remove the cable from the cache module. The cache module is backing up data, and data is lost if the cable is detached.
|
Disconnect the cable.
Slide the pack up and out of the DIMM baffle.
BBWC battery module replacement
|
NOTE:
|
The battery pack might have a low charge when installed. In this case, a POST error message is displayed when the server blade is powered up, indicating that the battery pack is temporarily disabled. No action is necessary on your part. The internal circuitry automatically recharges the batteries and enables the battery pack. This process might take up to four hours. During this time, the cache module functions properly, but without the performance advantage of the battery pack. |
Slide the pack and insert it into the DIMM baffle.
Connect the cable.
-
Parts return
If your part requires return then click on the appropriate link below:
|
|