HP Modular Cooling System - Overview
 Product Description
Figure 1: HP Modular Cooling System
|
HP Modular Cooling System or MCS is designed for high density server and blade deployments, re-circulates and cools the hot server exhaust air through heat exchangers residing in the MCS unit
|
Product Features
| Feature
|
Description
|
| Cooling Capacity of up to 30KW |
MCS has been designed to support a full load of blade servers, which, at their maximum configuration require a power load of 30KW. The MCS unit will provide over 2700 CFM of cool air distributed along the full height of the rack |
| Power Input Redundancy |
Automatically detects power failure and switches to alternate source. |
| Environmental Control and Safety |
The MCS features full environmental control of the cooled air temperature being placed in front of the servers. The heat exchanger unit features safety quick disconnect valves that prevent accidental chilled water leakage during service. A water leak detector ships standard with the MCS. Alarms can be sent via SNMP traps to Systems Insight Manager (SIM). |
| Hot-swappable components |
Fans and heat exchangers can be replaced while the unit is operating allowing for great flexibility in servicing the MCS. |
Link to Warranty Information
Link to QuickSpecs
Information for this Overview is taken from the product QuickSpecs. To access the complete QuickSpecs for this product, select the desired link from the following list:
|
|